Baxi Solo 3 PFL RangeWall Mounted Powered FlueGas Fired Central Heating UnitsInstallation and Servicing InstructionsPlease leave these instructions wi
4.0 Site Requirements104.1 Location1. The appliance may be fitted to any suitable wallwith the flue passing through an outside wall anddischarging to
4.0 Site Requirements114.3 Flue Position (Cont)WARNING - The addition of anything thatmay interfere with the normal operation of theappliance (e.g. FL
4.0 Site Requirements124.5 Ventilation of Compartments1. Where the appliance is installed in acupboard or compartment, no air vents arerequired.NOTE:
4.0 Site Requirement134.8 Flue Options1. The Baxi Solo 3 PFL can be fitted with fluesystems as illustrated.2, The standard flue is suitable only forho
5.0 Installation145.1 Initial Preparation1. Unpack contents of carton.2. Remove the lower door panel from the outercase. Remove the 2 screws holding t
5.0 Installation155.2 Fan Outlet Restrictor Rear Flue only up to 500mm (195/8in) 1. Release the four latches holding thecombustion box door (Fig 18).
5.0 Installation165.3 Position the Boiler1. Choose a suitable position for the boilermaking necessary allowances for the minimumclearances required (s
5.0 Installation175.5 Rear Flue PreparationWall thickness 285mm - 500mm (115/16- 193/8) goto section 5.6.Wall thickness 100mm - 284mm (4 in - 113/16in
5.0 Installation185.6 Assembly of Rear Flue1. Remove the rear air box blanking plate fromthe back plate by releasing the three screws (Fig. 30). 2. Re
5.0 Installation195.7 Fitting the Back Plate1. Engage the assembly into the hole previouslycut in the wall and slide in place (Fig. 34). 2. Secure the
2Baxi UK Limited is one of the leading manufacturersof domestic heating products in the UK. Our first priority is to give a high quality service to o
5.0 Installation205.8 Left or Right FlueConcentric flue kits are available to allow 3metres horizontal and 4 metres verticalflueing. Twin flue at 80mm
90mm (30, 40, 50)145mm (60, 70, 80)5.0 Installation215.9 Side Flue Preparation1. For both Left and Right Hand Flue - Measurethe distance from the wall
5.0 Installation225.10 Fitting the Flue and Back Plate1. NOTE: There are two options for fitting theflue and back plate they are:Method A - Fitting th
5.0 Installation235.11 Method A (Cont)7. Engage the assembly into the hole previouslycut in the wall and slide into place. 8. Secure the assembly to t
5.0 Installation245.12 Method B1. Remove the left or right hand air box blankingplate, as appropriate, from the back plate air boxby releasing the thr
5.0 Installation255.13 Terminal Guard1. When codes of practice dictate the use ofterminal guards, they can be obtained from mostplumbers and builders
5.0 Installation265.15 Internal Fitting Kit1. A internal fitting kit (available from merchants,quote Baxi Part No. 236441BAX) is suitable forwalls bet
5.0 Installation275.15 Internal Fitting Kit (Cont)6. Refit the end piece to the liner and open out tothe thickness of the wall. Seal the two piecestog
5.0 Installation285.16 Fitting the Combustion Box1. Offer up the combustion box to the back plateand locate the rear bottom edge of thecombustion box
5.0 Installation29NOTE: The method of connection to theelectricity supply must facilitate completeelectrical isolation of the appliance.Connection may
31.0 Introduction 42.0 Technical Data 53.0 System Details 74.0 Site Requirement 105.0 Installation 146.0 Commissioning the Appliance 327.0 Fitting t
5.0 Installation305.18 Making the Electrical Connections1. Remove the cover from the control box byremoving the 2 screws (Fig. 80).2. Slide the box fo
5.0 Installation315.19 Water Connections1. The boiler has two side water connections, thetop connection being FLOW and the bottomconnection being RETU
6.0 Commissioning the Appliance326.1 Commissioning the Appliance1. Flush the whole system in accordance with BS 5793 (see Section 3.1 Water Circulatin
6.0 Commissioning the Appliance336.1 Commissioning the Appliance (Cont)1. The burner pressure is factory set.2. From the table opposite check that the
7.0 Fitting the Outercase347.1 Fitting the Outercase1. The warning label may be removed unless theboiler is to be fitted within a cupboard.2. Taking t
8.0 Overheat Cut-off Device358.1 Operation1. The overheat cut-off device is of the manualreset type and therefore it is important that theuser knows h
9.0 Annual Servicing369.1 Dismantling the Boiler1. To ensure its continued safe and efficientoperation, it is important that the appliance isregularly
9.0 Annual Servicing379.2 Cleaning the Combustion Box1. Remove the burner assembly by pulling itforward (Fig. 103).2. Lightly brush any dirt from the
10.0 Changing Components38CentrePinRetainingRivetFig. 108Fig. 109Fig. 110Fig. 111Fig. 112Fig. 11310.1 Changing Components1. When changing components e
10.0 Changing Components3910.3 Ignition Electrode (Fig. 114)1. Disconnect the spark electrode lead at theelectrode. 2. Unscrew the electrode from the
Model Heat Output30 8.79kW (30,000 Btu/h)40 11.72kW (40,000 Btu/h)50 14.65kW (50,000 Btu/h)60 17.58kW (60,000 Btu/h)70 20.5kW (70,000 Btu/h)80 23.44kW
10.0 Changing Components4010.7 Changing Components (Cont)1. To change Fan - Pressure Switch - Burner -Burner Injector - Pilot Burner Injector - GasMan
10.0 Changing Components4110.10 Burner (Fig. 124)1. Remove the burner assembly by pulling itforward.2. Fit new burner and re-assemble all componentsin
11.0 Fault Finding42STARTReplace fanReplace harnessReplace pressureswitchReplace fanReplacethermostatDoes fan run ?Is there a clearconstant spark atth
11.0 Fault Finding43Replace the gasvalveReplace PCBBoiler satisfactorySet burner pressureto 16mbar ± 0.5Doesthe pilot burnerlight ?Doesthe main burner
12.0 Short Parts List445954901003433357783648498946942539112.1 Short Parts List35Key Description Model G.C. Manuf'rsNoNoPart No53 Burner 30-40-50
13.0 Notes45
13.0 Notes46
Baxi UK Limited manufacture a comprehensiverange of products for the domestic heating marketGas Central Heating Boilers(Wall, Floor and Fireside model
Baxi UK LimitedBrownedge RoadBamber Bridge PrestonLancashirePR5 6SNwww.baxi.comAfter Sales Service08706 096 096Technical Enquiries08706 049 049Comp No
2.0 Technical Data1 5Model 30 40 50 60 70 80P Heat Output kW 8.79 11.72 14.65 17.58 20.5 23.44Btu/h 30,000 40,000 50,000 60,000 70,000 80,000Q Heat In
2.0 Technical Data625751213924394422681441444107 Diawithout internalfitting117 Diawith internalfittingCentre ofGas Connection8 Slots20 x 6Layout of Fi
3.0 System Details7Typical SystemsArrangementOption ABoilerPumpAir VentRadiatorCircuitFully Pumped SystemAirVentRadiatorCircuitTwin ZoneValve SystemAi
3.0 System Details83.3 Pipework1. The sizes of flow and return pipes from theboiler should be determined by normal methods,according to the requiremen
3.0 System Details93.6 Sealed Systems (Fig. 9)1. SAFETY VALVE - A safety valve complyingwith the requirements of BS 6283 Part 1 must befitted close to