Baxi Duo-tec Combi 33 HE LPG Manual de Serviço

Consulte online ou descarregue Manual de Serviço para Aquecedores e fervedores de água Baxi Duo-tec Combi 33 HE LPG. Baxi Duo-tec Combi 33 HE LPG Technical data Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir

Resumo do Conteúdo

Página 1 - Duo-tec Combi HE LPG Range

© Baxi Heating UK Ltd 2010Duo-tec Combi HE LPG RangeGas Fired Wall Mounted CondensingCombination BoilerInstallation & Servicing InstructionsThese

Página 2 - Checklist

10© Baxi Heating UK Ltd 20104.0 Technical Data0200 400 600 800 1000 12000.511.522.533.54Metre (wg)Flow Rate (l/h)Pump - Available Head055.54.54.1 D

Página 3 - © Baxi Heating UK Ltd 2010

115.0 Dimensions and Fixings© Baxi Heating UK Ltd 2010DimensionsA 780mmB 345mmC 450mmD 116mm Ø Min.E 185mm(207mm for 80/125mm flue systems)F 145mmG 13

Página 4 - Legislation

126.0 System Details© Baxi Heating UK Ltd 20106.1 Information1. The Baxi Duo-tec Combi HE LPG Condensing CombinationBoiler is a ‘Water Byelaws Scheme

Página 5 - Safe Manual Handling

136.0 System Details© Baxi Heating UK Ltd 20106.5 System Filling and Pressurising1. A filling point connection on the central heating returnpipework m

Página 6 - CONTENTS

146.0 System Details© Baxi Heating UK Ltd 2010BoilerOther TapOutletsExpansionVessel*To HotTapsCheckValve*Pressure ReducerValve*Stop TapFig. 76.8 Domes

Página 7 - 1.0 Introduction

157.0 Site Requirements© Baxi Heating UK Ltd 20107.1 Location1. The boiler may be fitted to any suitable wall with the fluepassing through an outside

Página 8 - 2.0 General Layout

167.0 Site Requirement© Baxi Heating UK Ltd 20107.3 Ventilation of Compartments1. Where the appliance is installed in a cupboard orcompartment, no air

Página 9 - 3.0 Appliance Operation

177.0 Site Requirements© Baxi Heating UK Ltd 20107.7 Condensate DrainFAILURE TO INSTALL THE CONDENSATE DISCHARGEPIPEWORK CORRECTLY WILL AFFECT THE REL

Página 10 - 4.0 Technical Data

187.0 Site Requirements© Baxi Heating UK Ltd 20107.8 FlueNOTE: Due to the nature of the boiler a plume of watervapour will be discharged from the flue

Página 11 - Dimensions

198.0 Flue Options© Baxi Heating UK Ltd 20108.1 Horizontal Flue Systems1. The standard flue is suitable only for horizontaltermination applications.2.

Página 12 - 6.0 System Details

2© Baxi Heating UK Ltd 2010LPGBaxi Duo-tec Combi 24 HE LPGG.C.No47 075 48Baxi Duo-tec Combi 28 HE LPGG.C.No47 075 39Baxi Duo-tec Combi 33 HE LPGG.C.No

Página 13

208.0 Flue Options© Baxi Heating UK Ltd 2010VerticalFluesVertical Flues(Twin Pipe)XXYY8.2 Twin & Vertical Flue Systems1. Maximum permissible equiv

Página 14

218.0 Flue Options© Baxi Heating UK Ltd 2010ABK,K1RDCNU,WSLHJMEGFP8.3 Flue AccessoriesA2Key Accessory Size Code NoFLUE GROUP AConcentric Flue System 1

Página 15 - 7.0 Site Requirements

228.0 Flue Options© Baxi Heating UK Ltd 20108.4 Twin Flue Duct Adaptor1. The kit allows connection of a twin flue system to theboiler adaptor.8.5 Twin

Página 16 - 7.0 Site Requirement

238.0 Flue Options© Baxi Heating UK Ltd 20108.6 For Roof Terminals1. In the case of a pitched roof 25 - 50 degrees, position the leadtile to replace/f

Página 17

249.0 Plume Displacement© Baxi Heating UK Ltd 20109.1 Plume Displacement Kit (Fig. 14b)Kit No 5118638Content of kit1 0.9m 60/100 Concentric Flue1 1m 6

Página 18

259.0 Plume Displacement© Baxi Heating UK Ltd 2010Concentric 60/100 Flue60Ø ExhaustXYFig. 1720246810121460 Ø Exhaust (metres) XConcentric 60/100 Flue

Página 19 - 8.0 Flue Options

269.0 Plume Displacement© Baxi Heating UK Ltd 2010Min. 2 metresFig. 1950mmFlue TrimPosition of ‘Jubilee’ ClipscrewFig. 2430mm30mmFig. 21Fig. 23Fig. 20

Página 20

279.0 Plume Displacement© Baxi Heating UK Ltd 20109.3 General Fitting Notes (cont.)15. For aesthetic purposes it is permissible to route the60Ø exhaus

Página 21

2810.0 Installation© Baxi Heating UK Ltd 200710.1 Unpacking & Initial PreparationThe gas supply, gas type and pressure must be checked forsuitabil

Página 22

2910.0 Installation© Baxi Heating UK Ltd 201010.3 Fitting The Boiler1. Remove the sealing caps from the boiler connections.NOTE: A small amount of wat

Página 23 - 315mm 500mm

3Installer Notification Guidelines© Baxi Heating UK Ltd 2010Choose BuildingRegulations NotificationRouteContact your relevant LocalAuthority Building

Página 24 - 9.0 Plume Displacement

3010.0 Installation© Baxi Heating UK Ltd 201010.6 Fitting The FlueHORIZONTAL TELESCOPIC FLUE1. There are two telescopic sections, the TerminalAssembly

Página 25

3110.0 Installation© Baxi Heating UK Ltd 201010.6 Fitting the Flue (Cont)8. Adjust the two telescopic sections to dimension ‘Y’ (Fig. 41). Ensure that

Página 26

3210.0 Installation© Baxi Heating UK Ltd 201010.7 Making The Electrical ConnectionsThe boiler is fitted with a 1.3m length of 3 core cable. Thiscan be

Página 27 - 500mm Min

3311.0 Commissioning© Baxi Heating UK Ltd 201011.1 Commissioning the Boiler1. Reference should be made to BS:EN 12828 & 14336 whencommissioning th

Página 28 - 10.0 Installation

3411.0 Commissioning© Baxi Heating UK Ltd 201011.2 Check the Operational (Working) Gas Inlet Pressure1. Ensure that all controls are calling for heat,

Página 29

3512.0 Completion© Baxi Heating UK Ltd 201012.1 Completion 1. Instruct the user in the operation of the boiler andsystem, explaining the operational s

Página 30

3613.0 Servicing© Baxi Heating UK Ltd 2010Case Front PanelFig. 62Facia Panel SecuringScrewsFig. 63Inner DoorPanelFig. 64CondensateTrapSump13 .1 Annual

Página 31 - Dimension ‘Y’

3713.0 Servicing© Baxi Heating UK Ltd 201013.2 Annual Servicing - Inspection (Cont)6. Undo the nut on the gas inlet pipe to the venturi (Fig. 65)and p

Página 32

3814.0 Changing Components© Baxi Heating UK Ltd 2010IMPORTANT: When changing components ensure thatboth the gas and electrical supplies to the boiler

Página 33 - 11.0 Commissioning

3914.0 Changing Components© Baxi Heating UK Ltd 201014.3 Fan (Fig. 71)1. Undo the nut on the gas inlet pipe to the venturi (Fig. 49)and pull the sensi

Página 34

4Legislation© Baxi Heating UK Ltd 2010Codes of Practice - refer to the most recent versionIMPORTANT - Installation, Commissioning, Service & Repai

Página 35 - 12.0 Completion

4014.0 Changing Components© Baxi Heating UK Ltd 2010Fig. 74CoverBurnerGasketExtension Piece(Not on 33 & 40 models)CollectorVenturiHeatExchangerRea

Página 36 - 13.0 Servicing

4114.0 Changing Components© Baxi Heating UK Ltd 201014.8 Flue/Heat Exchanger Thermostat Sensor (Fig. 76)1. Ease the retaining tab on the sensor away a

Página 37

4214.0 Changing Components© Baxi Heating UK Ltd 201014.13 Pump - Head Only (Fig. 79)1. Drain the primary circuit and remove the socket headscrews secu

Página 38 - 14.0 Changing Components

4314.0 Changing Components© Baxi Heating UK Ltd 201014.16 Pressure Gauge (Figs. 82 & 83) 1. Drain the primary circuit and undo the nut on the

Página 39

4414.0 Changing Components© Baxi Heating UK Ltd 201014.19 Plate Heat Exchanger (Fig. 86)1. Drain the primary circuit and remove the gas valve asdescri

Página 40

4514.0 Changing Components© Baxi Heating UK Ltd 201014.21 P.C.B. (Fig. 90)1. Note the settings of the temperature control knobs,rotate them fully anti

Página 41

4614.0 Changing Components© Baxi Heating UK Ltd 201014.23 Gas Valve (Fig. 91)IMPORTANT: After replacing the valve the CO2must bechecked and adjusted a

Página 42

4715.0 Setting the Gas Valve© Baxi Heating UK Ltd 2010Selector SwitchDisplaybar01234Central Heating Temperature ControlDomestic Hot Water Temperature

Página 43

4816.0 Electrical© Baxi Heating UK Ltd 2010- brown- black- blue- whitebrbkbw- green- green / yellow- redgg/yr Control PCBX2 X3X9X5011212 3344556789X11

Página 44

4917.0 Short Parts List© Baxi Heating UK Ltd 2010Short Parts ListKey G.C. Description ManufacturersNo. No. Part No.311 Fan 5121447426 Motor 3 way Valv

Página 45

5Safe Manual Handling© Baxi Heating UK Ltd 2010GeneralThe following advice should be adhered to, from when first handling the boiler to the final stag

Página 46

5018.0 Fault Finding© Baxi Heating UK Ltd 2010NOTE: When instructed to turn theselector to the reset position turn theselector switch fully anticlockw

Página 47 - 15.0 Setting the Gas Valve

5118.0 Fault Finding© Baxi Heating UK Ltd 2010Refer to Section 16.0 “Illustrated Wiring Diagram” for position of terminals and componentsCentral Heati

Página 48 - 16.0 Electrical

5218.0 Fault Finding© Baxi Heating UK Ltd 2010Turn selector switch to The display illuminatesError 20, 28 or 50 flashingError 119 flashingB

Página 49 - 17.0 Short Parts List

5318.0 Fault Finding© Baxi Heating UK Ltd 2010Fault Finding Solutions SectionsIs there 230V at:Is there 230V at:Main terminals L and N Check electrica

Página 50 - 18.0 Fault Finding

5418.0 Fault Finding© Baxi Heating UK Ltd 2010Temperature sensors faulty.Cold resistance approximately10kΩ @ 25° C (DHW and CH sensors)20kΩ @ 25° C (F

Página 51

55© Baxi Heating UK Ltd 201018.0 Fault FindingCheck and correct if necessary1. The mechanical set of the gas valve(CO2 values - see instruction)2. Fla

Página 52

5619.0 Notes© Baxi Heating UK Ltd 2010

Página 53

5719.0 Notes© Baxi Heating UK Ltd 2010

Página 54

Failure to install and commission according to the manufacturer’s instructions and complete this Benchmark Commissioning Checklist will invalidate the

Página 55

Service RecordIt is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed.Service P

Página 56 - 19.0 Notes

6© Baxi Heating UK Ltd 2010CONTENTS1.0 Introduction 72.0 General Layout 83.0 Appliance Operation 94.0 Technical Data 105.0 Dimensions and Fixings 116.

Página 57

© Baxi Heating UK Ltd 2010UK Comp No5131787 - Iss 4 - 10/10BAXI A Trading Division of Baxi Heating UK Ltd (3879156)A Division of Baxi GroupBrooks Hous

Página 58 - CONDENSING BOILERS ONLY

71.0 Introduction© Baxi Heating UK Ltd 20101.1 Description1. The Baxi Duo-tec Combi HE LPG is a fully automatic gasfired wall mounted condensing combi

Página 59 - Service Record

82.0 General Layout© Baxi Heating UK Ltd 20102.1 Layout1. Expansion Vessel2. Automatic Air Vent3. DHW Plate Heat Exchanger4. Circulation Pump5. Drain

Página 60 - Website www.baxi.co.uk

93.0 Appliance Operation© Baxi Heating UK Ltd 20103.1 Central Heating Mode (Fig. 2)1. With a demand for heating, the pump circulates waterthrough the