© Baxi Heating U.K. Limited 2007.600B687/11INSTALLER GUIDEModel 339Heartbeat Oxysafe 2LIVE FUEL EFFECT GAS FIRE(GC No. 32-032-29)We trust that this gu
4.8 The minimum allowable distance from the outside of the appliance fascia to acorner wall having combustible material or any other combustible surfa
4.11 In the United Kingdom, as supplied, this appliance can be installed in thefollowing situations: -Note: A spigot extension is available (Baxi Fire
finished floor covering. Any opening visible below the appliance may be closed in butthe depth of the catchment space within the wall opening must be
*The total height of the closure plate is 660mm and will accommodate a maximumopening height of 650mm (This allows a 10mm overhang). Heights above623m
There must also be a minimum clearance of 165mm between the back of the closureplate and the back of the catchment space.On conventional flues the cat
5 PRE-INSTALLATION PREPARATION5.1 Unpacking.The carton contains the following:-1off Fire assembly.1off Ceramic fuel effect (In packaging inside fireb
5.3.5.Remove the control bezel by unscrewing twoscrews (See figure 6).5.3.6.Detach the fascia by removing the screws at thefascia sides (See figure 6)
required the opening should be completelysealed with tape.5.4.1 Hearth mounting(See figure 9).The closure plate must be fitted and sealedto the hearth
5.4.2 Wall mounting(See figure 10).The closure plate must be fittedand sealed to the hearth andfireplace opening using a suitableheat resistant materi
flue spigot opening are shown in figure 11. Mark these positions on the wall. The positions can alternatively be marked by placingthe fire in position
© Baxi Heating U.K. Limited 2007.All rights reserved. No part of this publication may be reproduced in any material form(including photocopying), stor
7 CONTROL AND PRESSURE CHECKS7.1 Check control settings.7.1.1 If closed, open the isolating valve at the inlet ‘T’ connector.7.1.2 To help in checking
7.3 Test for spillage.A spillage test must be made before the installed appliance is left with thecustomer.7.3.1 Close all doors and windows in the ro
7.4 Flame supervision and spillage monitoring system.The pilot unit incorporates a system which will automatically shut off the gas supply ifthe pilot
8.2.4 Explain to the customer that the appliance has a flame failure and spillagemonitoring system. Point out the explanation of this system shown in
recommend that you use a HEPA filtered vacuum to remove any dust and sootaccumulated in and around the fire before and after working on the fire. Do N
9.4 To remove the gas tap.9.4.1 Remove the fascia as section 9.2 above.9.4.2Detach the electrode lead from the pilot unit by pulling the lead down and
the tap.9.6.8 Refit the piezo generator.9.7 To remove an injector.9.7.1 Remove the fascia as section 9.2.9.7.2 Release the pipe compression fitting to
Safety First.Baxi Fires Division fires are CE Approved and designed to meet the appropriate BritishStandards and Safety Marks.Quality and Excellence.A
CONTENTSSection HeadingPage1 SAFETY 52 LIST OF ACCESSORIES 53 APPLIANCE DATA 64 GENERAL INSTALLATION REQUIREMENTS 84.11.2 Conventional firepla
1 SAFETYInstallerBefore continuing any further with the installation of this appliance please read the following guide to manual handling:! The lifti
3 APPLIANCE DATAThe appliance data label is on the inner face of the back panel at the lower left handside. It is visible when the fascia is removed.
The conversion of net efficiency to gross was achieved by multiplying the netefficiency by the following conversion factor from Table E3 of SAP 2005,
4 GENERAL INSTALLATION REQUIREMENTS4.1 The installation must be in accordance with these instructions.For the user’s protection, in the United Kingdo
4.3 Any chimney dampers or restrictors should be removed. If removal is notpossible they must be fixed in the open position.4.4 Normal adventitious v